Introducing HSL 25
1.4.6 I/O refreshing rate of an HSL system
The scan time unit for one slave index is set in 3/6/12 Mbps trans-
mission rate. Once the maximum slave address is set, the polling
cycle time of the HSL system is using the following formula:
Polling cycle time = maximum-address-of-slave * scan time unit
Table 1-5: Polling cycle time of HSL (Full Duplex Mode)
Note: Regardless of the transmission rate you select, the minimum
polling cycle time is 3×scan time unit, even when the maxi-
mum address is less than 3. Refer to Appendix A.
Maximum
address
Cycle Time
under 3 Mbps
Cycle Time
under 6 Mbps
Cycle Time
under 12 Mbps
5 303.33 µs 151.67 µs 75.83 µs
10 606.67µs 303.33 µs 151.67 µs
20 1.213 ms 606.67 µs 303.33 µs
30 1.820 ms 910.00 µs 455.00 µs
40 2.427 ms 1.213 ms 606.67 µs
50 3.033 ms 1.516 ms 758.33 µs
60 3.640 ms 1.820 ms 910.00 µs
63 3.822 ms 1.911 ms 955.50 µs